Manual – Fieldbus Interface INTERBUS UFI11A
21
5
INTERBUS Interface
Not all combinations are available. You will find the valid settings in the following table.
The insert with ID Code has to correspond to the setting of DIP switches 6 and 7. The
process data channel setting has to correspond to the setting of DIP switches 1-5. Any
conflicting settings will prevent operation of the INTERBUS. See also the section on con-
figuration of the Interbus interface via DIP switches.“
Program setting Function
ID Code 3 dez (03 hex) No parameter channel PCP
Process data
channel:
16 Bit 1 process data word (1 PD)
32 Bit 2 process Data Words (2 PD)
48 Bit 3 process data words (3 PD)
64 Bit 4 process data words (4 PD)
80 Bit 5 process data words (5 PD)
96 Bit 6 process data words (6 PD)
112 Bit 7 process data words (7 PD)
128 Bit 8 process data words (8 PD)
144 Bit 9 process data words (9 PD)
160 Bit 10 process data words (10 PD)
192 Bit 12 process data words (12 PD)
224 Bit 14 process data words (14 PD)
256 Bit 16 process data words (16 PD)
384 Bit 24 process data words (24 PD)
ID Code 227 dez (E3 hex) Parameter channel PCP: 1 word
Process data
channel:
16 Bit 1 process data word (Param + 1 PD)
32 Bit 2 process data words (Param + 2 PD)
48 Bit 3 process data words (Param + 3 PD)
64 Bit 4 process data words (Param + 4 PD)
80 Bit 5 process data words (Param + 5 PD)
96 Bit 6 process data words (Param + 6 PD)
112 Bit 7 process data words (Param + 7 PD)
128 Bit 8 process data words (Param + 8 PD)
144 Bit 9 process data words (Param + 9 PD)
176 Bit 11 process data words (Param + 11PD)
218 Bit 13 process data words (Param + 13 PD)
240 Bit 15 process data words (Param + 15 PD)
368 Bit 23 process data words (Param + 23 PD)