SHARP(CHINA)INVESTMENT CO.,LTD 
Main cause  Inspection method  Normal value/condition  Remedy 
Remote control not designed to allow 
fan speed change.
Check operation mode.
Fan speed should change ex- 
cept during dehumidifying ope- 
ration, sleep operation,internally 
normal operation 
Explain to user. 
4. Remote control signal is not received 
Main cause  Inspection method  Normal value/condition  Remedy 
Batteries at end of service life. Measure battery voltage. 
2.5 V or higher (two batteries in 
series connection) 
Install new batteries.
Batteries installed incorrectly. Check battery direction.
As indicated on battery 
compartment. 
Install batteries in indicated 
direction. 
Lighting fixture is too close, or 
fluorescent lamp is burning out.
Turn off light and check. Signal should be received when 
light is turned off.
Change light position or install 
new fluorescent lamp.
Operating position/angle is 
inap-propriate. 
Operate within range specified in 
manual.
Signal should be received within 
range specified in manual.
Explain appropriate handling 
to user.
Open-circuit or short-circuit in wiring 
of light receiving section. 
Check if wires of light receiving 
section are caught. 
Wires of light receiving section 
should not have any damage 
caused by pinching. 
Replace wires of light 
receiving section. 
Defective light receiving unit. 
Check signal receiving circuit  Tester  indicator  should  move 
when signal is received. 
Replace PCB. 
Dew condensation on light receiving 
unit. 
Check for water and rust.  Signal should be received within 
range specified in manual. 
Take moisture-proof measure 
for lead wire outlet of light 
receiving section. 
5. Vane do not move 
Main cause  Inspection method  Normal value/condition  Remedy 
Caught in sliding section. Operate to see if vane are caught 
in place.
Vane should operate smoothly.
Remove or correct catching 
section.
Disconnected connector (CN5 on 
relay PCB, louver motor side)
Inspect connectors. Connectors or pins should not 
be disconnected. 
Install correctly. 
Contact of solder on PCB(connector 
section on PCB)
Check visually. There should not be solder 
contact. 
Correct contacting section. 
6. Compressor does not start 
Main cause  Inspection method  Normal value/condition  Remedy 
Erroneous inter-unit connection. Check wiring between indoor and 
outdoor units.
Terminal board 1-N: 230 VAC, 
50 Hz
Correct wiring.
DamageD IPM Check IPM continuity Replace IPM
Main cause  Inspection method  Normal value/condition  Remedy 
Blown outdoor unit fuse. Check 20-A fuse.Check 15-A fuse. Fuse should not be blown. Replace fuse. 
Replace outdoor unit PWB 
assembly.
Power supply voltage is too low. Measure  power  supply  voltage 
during startup.
220±  10 VAC, 50 Hz   Make sure that power supply 
voltage is 198 V or higher.
Compressor lock. Supply current and touch com- 
pressor cover (sound absorbing 
material) to check if operation 
starts. 
Compressor should start nor- 
mally.
Apply external impact to 
compressor.Replace 
compressor.
3-7