SHARP(CHINA)INVESTMENT CO.,LTD 
9. Display E9 (Firstly display P0 or P9, then change to E9) 
Problem symptom  Display E9 (Firstly display P0 or P9, then change to E9) 
Cause  Intelligent power module of drive and module fault 
Malfunction No.  Content of diagnosis  Action 
If this code is displayed when the compressor is 
started for several seconds or even not started, 
check the compressor connection for correctness 
If no insert wrong, replace the intelligent power module 
Check if the outdoor module is 
tightly installed onto the radiating 
fins and if the silicone is applied 
evenly 
Fix the screws again if loose. 
Check the system pressure.  Recharge refrigerant if the pressure is low. Discharge 
some refrigerant if the pressure is too high. 
Check the outdoor ventilation and if 
there is any obstruction that affects 
the normal radiating of the air 
conditioner. 
Install to the position as required in the Insallation 
manual and ensure the air inlet and outlet of the outdoor 
unit is smooth. 
1 
 
Re-energize 
and check 
the 
protection 
code on 
display. 
Firstly 
display P0 
“P0” 
appears 
when the 
air 
conditioner 
is working 
The above inspections are normal, 
but the fault remains unsolved 
Replace the intelligent power module 
If this code is displayed when the compressor is 
started for several seconds or even not started, 
check the compressor connection for correctness 
If no insert wrong, replace the intelligent power module 
When the compressor is restarted immediately 
after stop, this might also cause P9 protection 
because the cooling system is not stable. 
Try starting the air conditioner again after a longer period 
of stop 
Cooling / heating is normal 
during run 
Replace the intelligent power module 
2 Re-energize 
and check 
the 
protection 
code on 
display. 
Firstly 
display P9 
P9 appears 
after the air 
conditioner is 
started and 
has run for a 
period of time 
If the cooling / heating is 
abnormal, check the 
compressor wiring for 
correctness. 
Insert again if loose. 
 
10. Display EE 
Problem symptom  Display EE 
Cause EEPROM fault 
Malfunction No.  Content of diagnosis  Action 
1  Shut off the power and suplyes again,if EE dispay again:  Replace outdoor power source board 
11. Display P1 
Problem symptom  Display P1 
Cause  Overvoltage / undervoltage protection 
Malfunction No.  Content of diagnosis  Action 
1  Test the supply voltage if it is between 160V  260V˄AC˅.  It is normal protection if exceeding this range. 
2  Test if the voltage between L and N terminal of outdoor unit is 
within 160V260V˄AC˅. 
It is normal protection if exceeding this range. 
3  If the voltage is normal  Replace the outdoor power source board 
 
12. Display E0ǃE5
3-15