[5] MALFUNCTION (PARTS) CHECK METHOD 
1. Procedure for determining defective outdoor unit IPM/compressor 
The following flow chart shows a procedure for locating the cause of a malfunction when the compressor does not start up and a DC overcurrent 
indication error occurs. 
 
 
 
 
 
 
                    No        No  
          
 d                        
 
            Yes         Yes 
                 
              No 
  
          Yes 
            Yes 
                            No 
  
No  
      Yes 
 
 
 
 
                    No         No         
                  
 
      Yes 
 
           No 
 
 
 
 
 
 
 
 
 
 
 
              Normal 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Use the remote operate   
the air conditioner 
Compressor starts up 
Does indoor unit LED   
display error code 
Normal 
P9 Does compressor start up
Does the wire 
conector right
conectes wire 
again 
Replace the 
inverter PCB 
Does low or high press valve 
open
Open  
Operates again after 3 mins 
Normal  Replace compressor 
P0
Does compressor start 
Does the wire 
conector right
conectes wire 
agrin 
Check indoor heat excharge 
and outdoor heat excharge
 
Clean indoor heat 
excharge or outdoor 
Check the refrigerant 
amount 
Check the installation 
condition 
Installation again 
Replace the inverter PCB 