EasyManuals Logo

SICK PBS Series User Manual

SICK PBS Series
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
Operating Instructions PBS
32 ©SICKAG•Germany•Allrightsreserved•Subjecttochangewithoutnotice8013154/U275/2010/02/01
Specications Model PBS
Internaltransmissionuid
Synthetic Oil
(onlyforpressureranges<0...10barand0 ... 25 bar abs)
Power supply L+ L+ in V DC 15 ... 35
Signal output and R
A
in Ohm 4 ... 20 mA, 3-wire R
A
0,5 k
maximum ohmic load R
A
0…10V,3-wire R
A
> 10 k
Adjustment zero point offset, max. 3 % of span
Setting time (Analogue signal) ms 3
Current consumption mA max. 100
Total current consumption mA max. 600 (max. 500 with IO-Link) incl. switching current
Switch points Individuallyadjustableviaexternalcontrolkeys
Type TransistorswitchingoutputPNPorNPN,withIO-Link:C/Q1:PNP
Number 1 or 2
Function
normallyopen/normallyclosed; windows- and hysteresis function freely
adjustable
Contact rating V DC SupplyvoltageL+-1V
Switching current mA Q1:250(withIO-Link:C/Q1:100),Q2:250
Response time ms 10
Accuracy % of span
0.5 (setting accuracy)
Insulationvoltage V DC 500
Display
Design 14-Segment-LED, blue 4-digits, height 9 mm
Range Electronic 180° rotatable
Accuracy % of span 1.0 ± 1 Digit
Update ms 1000, 500, 200, 100 (adjustable)
Accuracy % of span 1.0 *
)
*
)
Including non-linearity, hysteresis, zero point and full scale error (corresponds to
error of measurement per IEC 61298-2)
Non-linearity % of span ± 0.5 (BFSL) according to IEC 61298-2