It is only possible to access this setting through the PLC interface.
Characteristic Value
PROFINET access Start-up record SIG200 IO-Link Master (Slot 1, Subslot 1)
Byte 2, Bit 1: GDIAG (global diagnostics)
Encoding 0 Disable: All diagnostic messages from SIG200 to PLC
are disabled (default).
1 Enable: Diagnostic messages from SIG200 to PLC are
enabled.
7.1.2.2.1.3 Validation and data storage (Inspection Levels)
The validation and data storage settings (inspection levels) allow you to define the level
of compatibility check of a connected IO-Link Device. For more information regarding
usage and use cases, see "Data Storage", page 75.
Characteristic Value
PROFINET access Start-up record all IO-Link Device submodules (except “Digital
input”, “Digital output”; Slot 2, Subslot 2…5)
Byte 5: Validation and Backup
SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, Byte 5: Validation and
Backup
Encoding 0 No device check: No inspection is performed on this IO-
Link port regarding correct Device ID, Vendor ID or serial
number.
1 Type compatible Device (V1.0): Inspection is performed
on IO-Link port only regarding correct Device ID and Ven‐
dor ID.
2 Type compatible Device (V1.1): Inspection is performed
on IO-Link port regarding revision ID, Device ID, and Ven‐
dor ID.
3 Type compatible Device (V1.1) with Backup + Restore:
Inspection is performed on IO-Link port regarding revi‐
sion ID, Device ID, and Vendor ID. Data Storage (read
and write) allowed.
4 Type compatible Device (V1.1) with Restore: Inspection
is performed on IO-Link port regarding revision ID,
Device ID, and Vendor ID. Data Storage (write) allowed.
NOTE
Data storage requires that Expected Vendor and Device ID are set and match con‐
nected device for more information see "Data Storage", page 75.
7.1.2.2.1.4 Expected Vendor ID
Expected Vendor ID allows you to define Vendor ID that a connected IO-Link Device
must conform to.
NOTE
Vendor ID is only checked for Inspection Level “1”…”4”.