Characteristic Value
PROFINET access Start-up record all IO-Link Device submodules (except “Digital
input”, “Digital output”; Slot 2, Subslot 2…5)
Bytes 6…7: Expected Vendor ID
SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, Bytes 6…7: Expected
Vendor ID
Encoding Any Expected Vendor ID of IO-Link Device connected on IO-
Link Port (Unsigned Integer 16)
Example: Vendor ID SICK AG = 26
7.1.2.2.1.5 Expected Device ID
Expected Device ID allows you to define Device ID that a connected IO-Link Device must
conform to.
NOTE
Device ID is only checked for Inspection Level “1”…”4”.
Characteristic Value
PROFINET access Start-up record all IO-Link Device submodules (except “Digital
input”, “Digital output”; Slot 2, Subslot 2…5)
Bytes 8…11: Expected Device ID
SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, Bytes 8…11: Expected
Device ID
Encoding Any Expected Device ID of IO-Link Device connected on IO-
Link Port (Unsigned Integer 32)
Example:
Device ID
7.1.2.2.1.6 Port cycle time
Port cycle time allows you to define the minimum cycle time that the IO-Link Master will
use on a given IO-Link port.
Characteristic Value
PROFINET access Start-up record all IO-Link Device submodules (except “Digital
input”, “Digital output”; Slot 2, Subslot 2…5)
Byte 12: Port cycle time
SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, Byte 12: Port cycle time
Encoding 0 As fast as possible
16 1.6 ms
32 3.2 ms
48 4.8 ms
68 8.0 ms
100 20.8 ms
133 40 ms
158 80 ms
183 120 ms
7.1.2.2.1.7 Input data length
Input data length allows you to read out the current input data length (from a supplied
IODD or determined during IO-Link Device start-up).