NOTE
On PROFINET Input data length also contains the port qualifier information byte (PQI).
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, Byte 13: Input data
length
Encoding 0…33 Number of bytes in IO-Link Device Process Data In (via
PROFINET interface, including PQI byte)
7.1.2.2.1.8 Output data length
Output data length allows you to read out the current output data length (from a sup‐
plied IODD or determined during IO-Link Device start-up).
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index
0xB100 (Port S1)
0xB101 (Port S2)
0xB102 (Port S3)
0xB103 (Port S4)
Byte 14: Output data length
Encoding 0…32 Number of bytes in IO-Link Device Process Data Out
7.1.2.2.1.9 Port status info
Port status info allows you to read the connection status to an IO-Link Device on a given
IO-Link port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
0xB200 (Port S1)
0xB201 (Port S2)
0xB202 (Port S3)
0xB203 (Port S4)
Byte 3: Port status info
Encoding 0 Port running in IO-Link mode
1 Port in DI mode
2 Port in DO mode
3 Port deactivated
4 No device on port
5 Incorrect device on port
6 Fault
255 Info temporarily unavailable
7.1.2.2.1.10 Revision ID
Revision ID allows you to read out the IO-Link version of the IO-Link Device on this port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 7: RevisionID
Encoding 16 Version V1.0
17 Version V1.1