7.1.2.2.1.11 Transmission rate
Transmission rate allows you to read out the IO-Link data transmission rate on this port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 8: Transmission
rate
Encoding 0 No communication
1 COM1
2 COM2
3 COM3
7.1.2.2.1.12 Master cycle time
Master cycle time allows you to read out the actual cycle time on this port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 9: Master cycle
time
Encoding Bit 7…6 Time base
00 0.1 ms. Calculation: Multiplier x Time Base
01 0.4 ms. Calculation: Multiplier x Time Base + 6.4 ms
10 1.6 ms. Calculation: Multiplier x Time Base + 32 ms
Bit 5…0 Multiplier
7.1.2.2.1.13 Real Vendor ID
Real Vendor ID allows you to read out the actual Vendor ID of a connected IO-Link Device
on this port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Bytes 10…11: Real Ven‐
dor ID
Encoding Vendor ID of IO-Link Device connected on IO-Link Port (Unsigned
Integer 16)
7.1.2.2.1.14 Real Device ID
Real Device ID allows you to read out the actual Device ID of a connected IO-Link Device
on this port.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Bytes 12…15: Real
Device ID
Encoding Device ID of IO-Link Device connected on IO-Link Port (Unsigned
Integer 32)
7.1.2.2.1.15 Event entries
Event entries allows you to read out the number of supported event entries of a con‐
nected IO-Link Device on this port as well as the currently reported events.
NOTE
The amount of bytes for this function is dynamic, depending on the number of available
event entries (1 byte for the number of entries and 3 bytes for each entry).