NOTE
Encoding of each event entry follows the IO-Link event encoding. A value of 0x000000
in the first event entry indicates that no events are pending.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Bytes 16…N: Event
entries
Encoding Byte 16 Number of available event entries (Unsigned Integer 8,
maximum: 64)
Byte 17 First available event entry: EventQualifier
Table 6: Values of INSTANCE
Value Definition
0 Unknown
1 to 3 Reserved
4 Application
5 to 7 Reserved
Table 7: Values of SOURCE
Value Definition
0 Device (remote)
1 Master (local)
Table 8: Values of TYPE
Value Definition
0 Reserved
1 Notification
2 Warning
3 Error
Table 9: Values of Mode
Value Definition
0 Reserved
1 Event single shot
2 Event disappears
3 Event appears
Bytes
18…19
First available event entry: EventCode
Event codes are defined by the IO-Link Device vendor
The following bytes repeat the encoding of the first available event
entry
7.1.2.2.1.16 Profile entries
Profile entries allows you to read out the number of implemented IO-Link profiles of a
connected IO-Link Device on this port as well as all the profile identification numbers.