NOTE
The amount of bytes for this function is dynamic, depending on the number of imple‐
mented profile entries (1 byte for the number of entries and 2 bytes for each entry).
NOTE
The memory offset for Profile entries within the record depends on the number of event
entries (see "Event entries", page 36).
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Bytes N+1…N+M: Pro‐
file entries
Encoding Byte N
+1
Number of implemented profile entries (Unsigned Inte‐
ger 8, maximum: 32)
Byte N
+2…N
+3
First implemented profile identifier (Unsigned Integer 16)
The following bytes repeat the encoding of the first implemented
profile identifier
7.1.2.2.1.17 Process Data In valid
Process Data In valid allows you to read out if the current input process data of a given
IO-Link port is valid.
It is only possible to access this setting through the PLC interface.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 5, Bit 0: PDIV
(Process Data In valid)
Encoding 0 Process Data In is invalid
1 Process Data In is valid
7.1.2.2.1.18 Process Data Out valid
Process Data Out valid allows you to read out if the current output process data of a
given IO-Link port is valid.
It is only possible to access this setting through the PLC interface.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 5, Bit 1: PDOV
(Process Data Out valid)
Encoding 0 Process Data Out is invalid
1 Process Data Out is valid
7.1.2.2.1.19 IO Provider Status Input
This bit states the validity of the input data source.
Characteristic Value
PROFINET access SIG200 IO-Link Master (Slot 2, Subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, Byte 6, Bit 0: IOPSI
Encoding 0 Input Data Source invalid
1 Input Data Source valid
7 SIG200 CONFIGURATION
38
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200 8017853/2019-06-06 | SICK
Subject to change without notice