EasyManua.ls Logo

SICK SIG200 - Data Storage; Logic Editor

SICK SIG200
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<Datatype
xsi:type="UIntegerT"
bitLength="8">
</Variable>
Command HTTP
method
Request JSON
body
Response JSON
body
Function
iolink/sickv1/readDevice
(Process data)
POST {
"header": {
"portNumber": 0
},
"data": {
"processData":
"in"
}
}
{
"header": {
"status": 0,
"message": "Ok"
},
"data": {
"processDataIn": {
"1": false,
"2": false,
"3": false,
"4": false,
"5": false,
"6": false,
"7": false,
"8": false,
"9": false,
"10": false,
"11": 0,
"12": 726
},
"isValid": true
}
}
Returns the
segmented
and parsed
process data
contents of
a connected
IO-Link
Device.
portNumber:
0 = port 1, 1
= port 2, 2 =
port 3, 3 =
port 4
process‐
Data: in =
process data
in, out =
process data
out
process‐
DataIn /
process‐
DataOut:
structure of
process data
according to
IODD
isValid: true/
false
iolink/sickv1/writeDevice
(Process data)
POST {
"header":
{
"portNumber":0
}
,"data":
{
"process‐
DataOut":[0,55]
}
}
{
"header": {
"status": 0,
"message": "Ok"
}
}
Sets the raw
process data
(out) con‐
tents of a
connected
IO-Link
Device.
portNumber:
0 = port 1, 1
= port 2, 2 =
port 3, 3 =
port 4
process‐
DataOut:
structure of
process data
according to
IODD
SIG200 CONFIGURATION 7