As an alternative, you can connect the grounding conductor without cable lugs using a terminal
plate at the marked connection point.
Connecting the grounding conductor
Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free vaseline.
Arrange the flat washer and spring washer under the bolt head.
Check that the maximum permissible clamping thickness of 10 mm for the cable lug or strap
is not exceeded.
Fasten the clamping screw according to the following table. Screw-in depth and tightening
torque are different depending on whether cable lugs or ground terminals are used.
Screw Screw-in depth Tightening torque
When using cable lugs M6 > 6 mm 8 Nm
M8 > 8 mm 20 Nm
M12 x 25 > 16 mm 38 Nm
M16 x 35 > 20 mm 92 Nm
When using grounding
terminals
M6 > 9 mm 8 Nm
M8 > 12 mm 20 Nm
M10 > 15 mm 40 Nm
M12 > 18 mm 70 Nm
M16 > 20 mm 170 Nm
Use the connecting terminals designated for the grounding conductor in the terminal box.
6.3.5 Connect metal shield in the terminal box
If you are using metal-armored cables that are inserted into the terminal or auxiliary terminal
boxes with non-intrinsically safe circuits, then ground the metal shield in the terminal box.
Additional grounding points are permissible.
In terminal boxes with internal grounding part, connect the metal shield to the internal
grounding point.
In terminal boxes without internal grounding part, connect the metal shield to one of the
green-yellow grounding terminals.
6.3.6 Radio-frequency grounding for converter operation
In converter operation, the converter emits RF alternating currents. To establish and RF-
specific optimal connection between motor terminal box and motor enclosure, you can use
flexible braided copper flat cables with low impedance and a broad frequency range.
Establish the radio-frequency ground connection with flat cables. Alternatively you can
establish the radio-frequency ground connection with cable lugs.
Electrical connection
6.3 Preparation
SIMOTICS TN Series N-compact 1LA8
Operating Instructions 08/2017 73