EasyManua.ls Logo

Siemens 3VF Series

Siemens 3VF Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication System Manual 3WN6 Circuit-Breakers
ď›™ Copyright Siemens AG 1998. All rights reserved. Version1.0 (05/98)
48
T-Nr. Designation Message
address
Value range Value range Value range
1:x Setting values/
Protection
parameters
Releases
N and P
Releases
H and J/K
Releases
D and E/F
Note: Settable values/functions are highlighted in grey. The incremental settings for these values are
given on the next page.
x =
61 "a" release setting
current I
r
782, 1, 0, 22, 0 40 - 100 % I
n
(A) 40 - 100 % I
n
(A) 0; 40 - 100 % I
n
(A)
64 Time-lag class T
c
(trip
class)
38) 39)
782, 4, 0, 0, 0 0; 20 - 300
(0.1 s)
0; 20 - 300
(0.1 s)
20 - 300
(0.1 s)
65 "z" release setting
current I
d
782, 5, 0, 22, 0 200 - 40000 A 50 % I
n
- 12 I
n
(A) 125 % I
r
-12 I
r
(A)
66 "z" release delay t
d
782, 6, 0, 4,
130
20; 80 - 400 ms 20; 80 - 400 ms 20; 80 - 400 ms
71 "g" release setting
current I
g
783, 1, 0, 22, 0 160 - 1200 A 20 % I
n
-1200 A 20 % I
n
- 60 % I
n
(A)
72 "g" release delay t
g
783, 2, 0, 4,
130
100 - 500 ms 100 - 500 ms 100 - 500 ms
Messages 71 and 72 are only available with releases E/F, J/K and P.
81 "N" release setting
current I
N
785, 1, 0, 22, 0 20 % - 100 % I
n
(A) 20 % - 100 % I
n
(A) 20 % - 100 % I
n
(A)
82 "n" release setting
current I
i
785, 2, 0, 22, 0 150 % I
n
-
50000/65000 A
40
)
0; 150 % I
n
-12 I
n
0; 150 % I
n
-12 I
n
83 "g/N" release type I
g
/N 785, 3, 0, 0, 0 0 - 5 0 - 1 0 - 1
84 I
n, ext
External current
transformer
785, 4, 0, 22, 0 315 - 3200 A
Message 84 for P release only
85 Release time or
alarm t
x
41
)
785, 5, 0, 4,
130
0; 1 - 15 s 0; 1 - 15 s 0; 1 - 15 s
93 Current phase imbalance 790, 3, 0, 24, 0 0; 50 %
(5 - 50 % with
Z=F05)
0; 50 % 0; 50 %
101 Voltage phase
imbalance
792, 1, 0, 24, 0 0; 5 - 50 %
102 Reversal of direction of
power flow
792, 2, 0, 9, 3 0; -2000 kW to
+2000 kW
42)
Messages 101 - 106 are only available
for releases
103 Overfrequency f> 792, 3, 0, 28, 0 0; 15 - 500 Hz
N and P in conjunction with
the communication module with
104 Underfrequency f< 792, 4, 0, 28, 0 0; 15 - 500 Hz
measuring functions (Z=F05).
105 Overvoltage U> 792, 5, 0, 21, 0 0; 100 - 1000 V
106 Undervoltage U< 792, 6, 0, 21, 0 0; 100 - 1000 V
107 Load shedding 792, 7, 0, 24, 0 0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
38)
These time vaues are in the range 2 - 30 s. The transferred values (20 - 300) must therefore be multiplied by 0.1.
39)
The function is deactivated with setting value "0". This also applies to T-Nr. 1:93, 1:101 - 108.
40)
Size I (<= 1600 A): 50 kA; Size II (> 1600 A): 60 kA.
41)
t
x
is the time delay for the trip or warning signal for setting values with T-Nr. 1:93, 1:101 - 108. If t
x
= 0, the delay = 0 s. The setting values with
T-Nr. 1:93, 1:101 - 108 can also be deactivated by setting the value as a parameter. With Z=F05, these setting values can be parameterized
as either a trip or a warning, see T-Nr. 1:111, OS1:2.
42)
Supply from below: >0; Supply from above: <0.
108 Load input 792, 8, 0, 24, 0 0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)
0; 50 %-150 %
I
n
(A)

Table of Contents

Related product manuals