LOGO! Manual
A5E00067781 01
If the state at the Trg input remains 1 at least for the dura-
tion of the parameterized time T, the output is set to 1 after
the time T has elapsed (there is a delay between the input
being switched on and the output coming on).
If the state at the Trg input switches back to 0 before the
time T has elapsed, the time is reset.
The output is reset to 0 if the state at the Trg input is 0.
In the event of a power failure, the elapsed time is reset.
LOGO! Functions