2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
Manual, 04/2007, A5E01076883-01
13
Parameters
2
2.1 Parameters
Table 2-1 Parameters for analog input module
2AI TC ST Range of values Default setting Applicability
Group diagnostics (parameter
assignment error, internal error)
• Disable
• Enable
Disable Module
Diagnostics: Overflow/underflow
• Disable
• Enable
Disable Module
Diagnostics: Wire-break check
*
• Disable
• Enable
Disable Channel
Smoothing
• None
• Weak
• Medium
• Strong
None Channel
Comparison point
• None
• RTD
None Channel
Reference junction number
• None
• 1 to 8
(in the case of the IM151-1
STANDARD and IM151-1 FO
STANDARD)
• 1
(in the case of the IM151-1
BASIC, IM151-1 COMPACT,
IM151-1 HIGH FEATURE)
None Module
Type/range of measurement
• Deactivated
• Voltage ± 80 mV
• TC-EL Type T (Cu-CuNi)
• TC-EL Type K (NiCr-Ni)
• TC-EL Type B (PtRh-PtRh)
• TC-EL Type N (NiCrSi-NiSi)
• TC-EL Type E (NiCr-CuNi)
• TC-EL Type R (PtRh-Pt)
• TC-EL Type S (PtRh-Pt)
• TC-EL Type J (Fe-Cu-Ni)
• TC-EL Type L (Fe-Cu-Ni)
TC-EL Type K (NiCr-
Ni)
Channel
*
Only with thermocouples. A parameter assignment error occurs when the wire break diagnosis is enabled in the voltage
measuring range. The module does not start up.