Connecting
5.1 Connecting measuring sensors
2AI TC ST analog electronic module (6ES7134-4JB00-0AB0)
26 Manual, 04/2007, A5E01076883-01
Abbreviations used
The meanings of the abbreviations in the figures below are as follows:
M+: Measuring line (positive)
M- Measuring line (negative)
M
ANA
Reference potential of the analog measuring circuit
M Ground connection
L+ Rated load voltage 24 V DC
U
CM
Potential difference between inputs and reference potential of the measuring
circuit M
ANA
U
ISO
Potential difference between M
ANA
and central grounding point
Isolated measuring encoders
The isolated measuring encoders are not connected to the local ground potential. These can
be potential-free. Depending on local conditions or interference, potential differences U
CM
(static or dynamic) can occur between the measuring lines M- of the input channels and the
reference point of the measuring circuit M
ANA
.
To ensure that the permitted value for U
CM
is not exceeded in environments with strong EMC
interference, the following applies:
For the 2AI TC analog input module: Connect M- to M
ANA
!
The following schematic representation illustrates the connection of isolated measuring
encoders to the optically isolated analog input modules.
1
2
3
4
5
6
0
0
/
0
0
$1$
0
0
$'8
8
,62
8
&0
Logic
Backplane bus
Ground bus
Central grounding point
Recommended connection
Isolated measuring encoders