5/7
Siemens plc 1993
P05 RUN/STOP mode 000 Ramp–down; edge–triggered; trip inactive.
(000)
Parameter
Number
Description
Display
Setting
Notes
(Factory
Setting)
P04
(000)
(continued)
Note: Additional fixed frequencies are
programmable using parameter P24, which
overrides this operating mode.
(see section 5.1.1 for
detailed explanation)
001 Ramp–down; level–triggered; trip inactive.
002 Free run; edge–triggered; trip inactive.
003 Free run; level–triggered; trip inactive.
004 Ramp–down; edge–triggered; trip active.
005 Free run; edge–triggered; trip active.
006 Ramp–down; level–triggered; trip active.
001 Linear 0–60 Hz
100% 60–400 Hz
P06 Voltage to frequency curve
selection
VOLTAGE
FREQUENCY
50
100
000 Linear 0–50 Hz
100% 50–400 Hz
400
VOLTAGE
FREQUENCY
60
100
400
007
008 Ramp–down; push–button control.
009 Free run; push–button control.
Free run; level–triggered; trip active.
007
008
009
0 V = minimum frequency P07.
10 V = maximum frequency P08.
0 mA = minimum frequency P07.
20 mA = maximum frequency P08.
4 mA = minimum frequency P07.
20 mA = maximum frequency P08.
0–10 V input (X11.7)
0–20 mA input (X11.9)
4–20 mA input (X11.9)
Analogue Inputs
VOLTAGE
87
100
002 Linear 0–87 Hz
100% 87–400 Hz
FREQUENCY
400

Table of Contents