Operator Control  09.02 
6-2  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
6.2 Displays   
Tables 6.2 and 6.3 below give an overview of the displays that can be shown on the PMU: 
    Parameter number  Index  Parameter value 
    e.g.  e.g.  e.g. 
Basic converter 
 
Visualization 
parameters 
Technology board 
 
   
Basic converter 
 
Setting 
parameters 
Technology board 
 
   
Table 6.2  Displaying visualization and setting parameters on the PMU 
 
 
Actual value
 
Parameter value 
not (yet) 
possible
 
Alarm
 
Fault
 
Display
 
 
   
 
Table 6.3  Status display on the PMU 
NOTE 
The parameters are described in Chapter 5 and the fault and alarm messages are described in Chapter 7. 
 
Once the electronics supply voltage has been switched on, either the PMU operating display shows the current 
operating state of the rectifier/regenerating unit (e.g. o009) or a fault or alarm message is displayed (e.g. F060). 
The operating states are described in Section 5.1 and the fault and alarm messages are described in Sections 
7.1 and 7.2. 
As described in Section 6.3 (Figures 6.2 and 6.3), it is possible to change over from one display level to 
another. 
By pressing <P>, it is possible to change from the status display (e.g. o009) to the parameter number level in 
which the separate parameters can be selected via <raise> or <lower>. The selected access level (P051) and 
the operating state (r000, r001) determine here which parameters are displayed. All parameters are not always 
visible (see Chapter 5/overview of the abbreviations/footnotes 5 to 8)! 
Pressing <P> again switches to the index level for indexed parameters (see Section 4.1.2) but directly to the 
parameter value level for all other parameters and the index or the value can be modified via <raise> and 
<lower>. The same conditions apply for changing a parameter value as were described for the parameter 
number, i.e. a parameter value can only be modified under an appropriate access level and an appropriate 
operating state. 
If the 4 characters of the seven-segment display are insufficient for displaying a parameter value, only 4 figures 
will be displayed initially (see Figure 6.4). The presence of further figures to the right or left of this "window" is 
indicated by flashing of the left-hand or right-hand figure. If <P>+<lower> or <P>+<raise> are pressed 
simultaneously, this "window" can be moved to view the parameter value. 
By pressing <P> again, it is possible to switch back to the parameter number level.. 
AoteWell Automation Sales Team
Buy Siemens PLC HMI Drives at AoteWell.com