Start-Up  09.02 
4-22  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
Bits 20 to 22: reserved 
Bit 23:  12-pulse mode selection command (H  "12-pulse mode is selected") 
The command is executed with an H signal and causes a change in operational behavior from that of a single 
unit (i.e. a "normal" single unit becomes a 12-pulse master or a 12-pulse slave depending on parameter P587 
or control word bit 27). See Section 3.8.4 for further details. 
Bits 24 and 25: reserved 
Bit 26:  Fault, external 2 command (L "Fault, external 2") 
The command is recognized with an L signal and does not become active until the pre-charging time (P329) 
and an additional time delay of 3000 ms has elapsed when the operating mode RUN is active. During formation 
(P052=20) or circuit identification (P052=21), the command is ineffective. 
After the command has been accepted 
♦  Changeover to the FAULT status (007) (fault F036) 
The firing pulses are inhibited and the main contactor, if installed, drops out (see also Chapter 7 "Faults and 
Warnings"). 
Bit 27:  Master/slave changeover (H  "Slave S/F unit"/L  "Master S/F unit") 
The command switches between slave and master mode. 
Slave S/F unit:   The closed-loop control operates with an external DC link current setpoint 
Even when a thyristor test is selected (P353=1, 2 or 3) if Ud > 5% it does not
 wait in 
state 
o
012 and the thyristor test is not carried out. 
Master S/F unit:   The closed-loop control operates with an external DC link current setpoint 
Bit 28:  Alarm, external 1 command (L "Alarm, external 1") 
The command is executed with an L signal. 
After the command has been accepted 
♦  The operating status is retained. An alarm message (A015) is output (also refer to Section 7 "Fault and 
Alarm Messages")
 
Bit 29:  Alarm, external 2 command (L "Alarm, external 2") 
The command is executed with an L signal. 
After the command has been accepted: 
♦  The operating status is retained. An alarm message (A015) is output (also refer to Section 7 " Fault and 
Alarm Messages ")
 
Bit 30:  Selection, basic/reserve setting command (L "Basic setting / H "Reserve setting") 
The command activates the BASIC SETTING with an L signal and the RESERVE SETTING with an H signal 
After the command has been accepted: 
♦  The parameter settings of the basic or reserve setting for the control word itself, the setpoint channel, and 
the closed-loop control are activated  (see "Data sets" in Section 4.1.2 and "Selecting the data sets" in 
Section 4.4).
 
Bit 31:  Main contactor checkback signal command (H "Main contactor checkback signal") 
This command permits you to include an auxiliary contact of the main contactor in the unit control circuit (an H 
signal implies that the main contactor has picked up). 
After the command has been accepted: 
♦  An operating status > 