Parameter List  09.02 
5-36  Siemens AG    6SE7087-6AK85-1AA0 
  Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory- 
setting 
See 
Modify 
(access / 
status) 
5.14 Modulator 
P773 Deadband Convert 
The reversing threshold of the auto-reversing module (in rectifier direction) 
 
If the (signed) setpoint of the DC link current (output of the DC link voltage 
controller on the output side of the limiting module) exceeds
 the value of + 
0.05% set with this parameter, the firing pulses of the rectifier bridge are 
enabled. These pulses are inhibited if the setpoint of the DC link current 
drops below the value set here. 
 
RDS parameter 
 
PNU=305Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.01 % 
0.01 to 100.00 
[%] 
4 
0.01 
3/    BR 
3/    BR 
P774 
** 
Deadband Invert 
The reversing threshold of the auto-reversing module (in regenerating 
direction) 
If the (signed) setpoint of the DC link current (output of the DC link voltage 
controller on the output side of the limiting module) exceeds
 the value of - 
0.05% set with this parameter, the firing pulses of the rectifier bridge are 
enabled. These pulses are inhibited if the setpoint of the DC link current 
drops below the value set here.. 
 
RDS parameter 
 
PNU=306Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.01 
-100.00 to -0.01 
[%] 
4 
-3.00 
3/    BR 
3/    BR 
P775  Min Gating Angle 
Alpha G limit (rectifier stability limit) 
 
RDS parameter 
 
PNU=307Hex; Type=O2; Scaling: 1Hex 
=
∧
 1 °el 
0 to 120 
[°el] 
4 
0 
3/    BR 
3/    BR 
P776  Max Gating Angle 
Alpha W limit (inverter stability limit) 
 
RDS parameter 
 
PNU=308Hex; Type=O2; Scaling: 1Hex 
=
∧
 1 °el 
120 to 165 
[°el] 
4 
150 
3/    BR 
3/    B 
P777  Max Gating Angle Ramp 
Transition ramp of the alpha W limit from pulsating to continuous DC (for 
currents < pulsating threshold, the control angle is limited to 165°, for 
currents > (pulsating threshold+P777) to P776 with linear interpolation 
inbetween) 
 
RDS parameter 
 
PNU=309Hex; Type=O2; Scaling: 1Hex 
=
∧
 1 % 
0.00 to 100.00 
[%] of P075 
4 
20.00 
3/    BR 
3/    BR 
 