Siemens PM240-2_EN_rev00-30082019.docx    3-11 
Table 4 Technical data PM240-2, FSD (3 AC 380 V to 480 V ±10 %) 
PM240-2  with  integrated  line  filter     
code 
Output current 
Rated current In 
Base-load current IH  
Peak current Imax (3s over 300s) 
Peak current Imax (57+3s over 300s) 
Type rating¹) 
on basis of In 
on basis of IH 
Sound pressure level LpA (1m) 
24 V DC supply 
for the Control Unit 
Rated input current²) 
with integrated line reactor 
Class J UL fuses 
Rated current 
NH fuses IEC 60947 
Rated current 
Circuit breaker type designation IEC 
60947 
Rated current 
3VL1712-
1DD33-0AA0 
100 …125 
Resistance value  
ext. braking resistor 
Max. cable length  
to braking resistor 
Line supply connection  
L1, L2, L3 
Tightening torque 
Screw terminals 
10.00…35.00mm
2
 (20 … 10 AWG) 
2.5 … 4.5 Nm 22 lbf in 
Motor connection 
U2, V2, W2 
Tightening torque 
Screw terminals 
10.00…35.00mm
2
 (20 … 10 AWG) 
2.5 … 4.5 Nm 22 lbf in 
DC link connection, connection for 
braking resistor 
DCP/R1, DCN, R2 
 
2,50…16,0mm
2 
(AWG20… AWG6) 
Max. motor cable length ³) 
shielded/unshielded 
Weight 
with integrated line filter 
¹) Rated power of a typical standard induction motor at 400 V 3 AC 
²) The input current depends on the motor load and line impedance. The input currents apply for a load with 
the type rating (based on In) for a line impedance corresponding to uk = 1%. 
³)  Max.  motor  cable  length  200  m  (shielded)  for  PM240-2  Power  Modules  with  integrated  line  filter  to 
maintain the limit values of EN 61800-3 Category C2.