3-12 Siemens PM240-2_EN_rev00-30082019.docx
Table 5 Technical data PM240-2, FSE(3 AC 380 V to 480 V ±10 %)
PM240-2 with integrated line filter code
Output current
Rated current In
Base-load current IH
Peak current Imax (3s over 300s)
Peak current Imax (57+3s over 300s)
Type rating¹)
on basis of In
on basis of IH
Sound pressure level LpA (1m)
24 V DC supply
for the Control Unit
Rated input current²)
with integrated line reactor
Class J UL fuses
Rated current
NH fuses IEC 60947
Rated current
Circuit breaker type designation IEC 60947
Rated current
3VL1716-1DD33-
0AA0
125 … 160
3VL3720-1DC36-
0AA0
160 … 200
Resistance value
ext. braking resistor
Max. cable length
to braking resistor
Line supply connection
L1, L2, L3
Tightening torque
Screw terminals
25…70mm
2
(6 … 3/0 AWG,)
10 Nm 88.5 lbf in
Motor connection
U2, V2, W2
Tightening torque
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
10,00…35,00mm
2
(AWG8… AWG2)
Max. motor cable length ³)
shielded/unshielded
Weight
with integrated line filter
¹) Rated power of a typical standard induction motor at 400 V 3 AC
²) The input current depends on the motor load and line impedance. The input currents apply for a load with
the type rating (based on In) for a line impedance corresponding to uk = 1%.
³) Max. motor cable length 200 m (shielded) for PM240-2 Power Modules with integrated line filter to
maintain the limit values of EN 61800-3 Category C2.