Siemens PM240-2_EN_rev00-30082019.docx 3-13
Table 6 Technical data PM240-2, FSF(3 AC 380 V to 480 V ±10 %)
PM240-2 with integrated line filter
code
Output current
Rated current In
Base-load current IH
Peak current Imax (3s over 300s)
Peak current Imax (57+3s over 300s)
Type rating¹)
on basis of In
on basis of IH
Sound pressure level LpA (1m)
24 V DC supply
for the Control Unit
Rated input current²)
with integrated line reactor
Class J UL fuses
Rated current
NH fuses IEC 60947
Rated current
Circuit breaker type designation IEC
60947
Rated current
3VL3720-
1DC36-0AA0
160 … 200
3VL3725-
1DC36-0AA0
200 … 250
3VL3720-
1DC36-0AA0
200 … 250
3VL4731-
1DC36-0AA0
250 … 315
Resistance value
ext. braking resistor
Max. cable length
to braking resistor
Line supply connection
L1, L2, L3
Tightening torque
Cable lug according to SNL71322 for M10 bolts
35.00 …2 x 120mm
2
(1 AWG … 2 × 4/0 AWG)
22…25Nm 10 lbf.in
Motor connection
U2, V2, W2
Tightening torque
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length ³)
shielded/unshielded
Weight
with integrated line filter
¹) Rated power of a typical standard induction motor at 400 V 3 AC
²) The input current depends on the motor load and line impedance. The input currents apply for a load with
the type rating (based on Irated) for a line impedance corresponding to uk = 1%.
³) Max. motor cable length 300 m (shielded) for PM240-2 Power Modules with integrated line filter to
maintain the limit values of EN 61800-3 Category C2.