Table 3: In Line, 200 – 460 Volt starter ratings
HP @
200V
HP @
230V
HP @
460V
Rated
Current
(Amps)
Overload
Range
(Amps)
Current Limit
Range
(Amps)
Manufacturer
Catalog
Number
- 5 10 18 6 – 25 24 – 85 72GG34AFP
5 7.5 15 22 8 – 30 28 – 103 72HG34AFP
7.5 10 20 28 10 – 39 36 – 135 72JG34AFP
7.5 10 25 35 13 – 49 45 – 166 72KG34AFP
10 15 30 42 15 – 57 53 – 196 72LG34AFP
15 20 40 55 20 – 75 70 – 257 72MG34AFP
20 25 50 68 24 – 93 87 – 319 72NG34AFP
25 30 60 80 29 – 112 104 – 382 72PG34AFP
In Line
Configuration
40 50 - 130 48 – 181 168 - 618 72RG32AFP
Table 4: In Line, 460 - 575 Volt starter ratings
HP @
460V
HP @
575V
Rated
Current
(Amps)
Overload
Range
(Amps)
Current Limit
Range
(Amps)
Manufacturer
Catalog
Number
10 15 18 6 – 25 24 – 85 72GG35AFP
15 20 22 8 – 30 28 – 103 72HG35AFP
20 25 28 10 – 39 36 – 135 72JG35AFP
25 30 35 13 – 49 45 – 166 72KG35AFP
30 40 42 15 – 57 53 – 196 72LG35AFP
40 50 55 20 – 75 70 – 257 72MG35AFP
50 60 68 24 – 93 87 – 319 72NG35AFP
In Line
Configuration
60 75 80 29 – 112 104 – 382 72PG35AFP