Functions
2.7 Motor Protection (Motor Starting Protection 48, Motor Restart Inhibit 66, Load Jam Protection)
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
147
Example:
Motor with the following data:
The setting for address 4402 Load Jam I> as secondary value is calculated as follows:
The tripping delay time can remain at the default setting of 1 s. The warning threshold is set to 75% of the trip-
ping element (4404 I Alarm 0.95 A sec.).
The tripping delay time can remain at the default setting of 2 s.
In order to block the function during motor startup, the parameter 4406 T Start Blk. is set to double startup
time (T Start Blk. = 2 · 8.5 s = 17 s).
Nominal voltage V
Nom
= 6600 V
Nominal current I
Nom
= 126 A
Long-term current rating I
max
= 135 A
Startup duration T
startmax.
= 8.5 s
Current transformer I
NomCTprim
/ I
NomCTsec
= 200 A / 1 A