Functions
2.1 General
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
57
2.1.6.3 Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.1.6.4 Information List
Addr. Parameter C Setting Options Default Setting Comments
1101 FullScaleVolt. 0.10 .. 800.00 kV 20.00 kV Measurem:FullScaleVolt-
age(Equipm.rating)
1102 FullScaleCurr. 10 .. 50000 A 400 A Measurem:FullScaleCur-
rent(Equipm.rating)
1107 I MOTOR START 1A 0.40 .. 10.00 A 2.50 A Motor Start Current (Block
49, Start 48)
5A 2.00 .. 50.00 A 12.50 A
1108 P,Q sign not reversed
reversed
not reversed P,Q operational measured
values sign
No. Information Type of In-
formation
Comments
126 ProtON/OFF IntSP Protection ON/OFF (via system port)
356 >Manual Close SP >Manual close signal
501 Relay PICKUP OUT Relay PICKUP
511 Relay TRIP OUT Relay GENERAL TRIP command
533 Ia = VI Primary fault current Ia
534 Ib = VI Primary fault current Ib
535 Ic = VI Primary fault current Ic
561 Man.Clos.Detect OUT Manual close signal detected
4601 >52-a SP >52-a contact (OPEN, if bkr is open)
4602 >52-b SP >52-b contact (OPEN, if bkr is closed)
16019 >52 Wear start SP >52 Breaker Wear Start Criteria
16020 52 WearSet.fail OUT 52 Wear blocked by Time Setting Failure
16027 52WL.blk I PErr OUT 52 Breaker Wear Logic blk Ir-CB>=Isc-CB
16028 52WL.blk n PErr OUT 52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir