Technical Data
4.6 Dynamic Cold Load Pickup
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
375
4.6 Dynamic Cold Load Pickup
Timed changeover of settings
Setting Ranges / Increments
Controlled elements Non-directional time overcurrent protection (separate phase
and ground settings) 50(N), 51(N)
Initiation criteria Current criterion BkrClosed I MIN
Interrogation of the circuit breaker position
Binary input
Time control 3 time elements
(T
CB Open.
, T
Active
, T
Stop)
Current control Current threshold BkrClosed I MIN (reset on current falling
below threshold: monitoring with timer)
Current Control for I
Nom
= 1 A 0.04 A to 1.00 A Increments
0.01 A
for I
Nom
= 5 A 0.20 A to 5.00 A
Time Until Changeover To Dynamic Settings
T
CB OPEN
0 s to 21600 s (= 6 h) Increments 1 s
Period Dynamic Settings are Effective After a
Reclosure T
Active
1 s to 21600 s (= 6 h) Increments 1 s
Fast Reset Time T
Stop
1 s to 600 s (= 10 min) or (fast reset inactive) Increments 1 s
Dynamic Settings of Pickup Currents and
Time Delays or Time Multipliers
Adjustable within the same ranges and with the same incre-
ments as the directional and non-directional time overcurrent
protection