2.13 Dir. Intermittent earth fault protection
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
214
Figure 2-77 Activation of the directional intermittent ground fault protection
Fault Log, Ground Fault Log, Fault Recording
Parameter Dir. Interm. EF allows you to define the type of fault handling and fault logging. If set to ON,
tripping is possible and a fault log is generated. If set to ON with GF log, tripping is possible, a fault log and
a ground fault log are generated. If set to Alarm Only, no tripping is possible. Only an alarm is generated.
Furthermore, only a ground fault log is created.
The raising pickup of the function (indication 6972 „dIEF pick up“) is the criterion for opening the ground
fault log.