33
140 46 Disabled
TOC ANSI
TOC IEC
Definite Time
Disabled 46 Negative Sequence Protection
141 48 Disabled
Enabled
Enabled 48 Startup Time Supervision for
Motors
142 49 Disabled
No ambient temp
With amb. temp.
No ambient temp 49 Thermal Overload Protection
143 66 #of Starts Disabled
Enabled
Enabled 66 Startup Counter for Motors
144 Load Jam Prot. Disabled
Enabled
Enabled Load Jam Protection
150 27/59 Disabled
Enabled
Disabled 27, 59 Under/Overvoltage Protec-
tion
154 81 O/U Disabled
Enabled
Disabled 81 Over/Underfrequency Protec-
tion
170 50BF Disabled
Enabled
enabled w/ 3I0>
Disabled 50BF Breaker Failure Protection
172 52 B.WEAR MONIT Disabled
Ix-Method
2P-Method
I2t-Method
Disabled 52 Breaker Wear Monitoring
182 74 Trip Ct Supv Disabled
2 Binary Inputs
1 Binary Input
Disabled 74TC Trip Circuit Supervision
190 RTD INPUT Disabled
Enabled
Disabled External Temperature Input
191 RTD CONNECTION 6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD Eth
12 RTD Eth
Int.Temp.Meas.
6 RTD HDX Ext. Temperature Input Connec-
tion Type
192 Cap. Volt.Meas. NO
YES
NO Capacitive voltage measurement
Addr. Parameter Setting Options Default Setting Comments