A.7 Functional Scope
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
453
170 50BF Disabled
Enabled
enabled w/ 3I0>
Disabled 50BF Breaker Failure Protection
172 52 B.WEAR MONIT Disabled
Ix-Method
2P-Method
I2t-Method
Disabled 52 Breaker Wear Monitoring
182 74 Trip Ct Supv Disabled
2 Binary Inputs
1 Binary Input
Disabled 74TC Trip Circuit Supervision
190 RTD INPUT Disabled
Enabled
Disabled External Temperature Input
191 RTD CONNECTION 6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD Eth
12 RTD Eth
Int.Temp.Meas.
6 RTD HDX Ext. Temperature Input Connec-
tion Type
192 Cap. Volt.Meas. NO
YES
NO Capacitive voltage measurement
617 ServiProt (CM) Disabled
T103
DIGSI
RTD-RS485
T103 Port B usage
- FLEXIBLE FUNC. 1...20 Flex. Function 01
Flex. Function 02
Flex. Function 03
Flex. Function 04
Flex. Function 05
Flex. Function 06
Flex. Function 07
Flex. Function 08
Flex. Function 09
Flex. Function 10
Flex. Function 11
Flex. Function 12
Flex. Function 13
Flex. Function 14
Flex. Function 15
Flex. Function 16
Flex. Function 17
Flex. Function 18
Flex. Function 19
Flex. Function 20
Please select Flexible Functions
Addr. Parameter Setting Options Default Setting Comments