Appendix
A.8 Settings
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
461
1801 50c-2 PICKUP ColdLoadPickup 1A 0.10 .. 35.00 A; 10.00 A 50c-2 Pickup
5A 0.50 .. 175.00 A; 50.00 A
1802 50c-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 50c-2 Time Delay
1803 50c-1 PICKUP ColdLoadPickup 1A 0.10 .. 35.00 A; 2.00 A 50c-1 Pickup
5A 0.50 .. 175.00 A; 10.00 A
1804 50c-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.30 sec 50c-1 Time Delay
1805 51c PICKUP ColdLoadPickup 1A 0.10 .. 4.00 A 1.50 A 51c Pickup
5A 0.50 .. 20.00 A 7.50 A
1806 51c TIME DIAL ColdLoadPickup 0.05 .. 3.20 sec; 0.50 sec 51c Time dial
1807 51c TIME DIAL ColdLoadPickup 0.50 .. 15.00 ; 5.00 51c Time dial
1808 50c-3 PICKUP ColdLoadPickup 1A 1.00 .. 35.00 A; ∞∞A 50c-3 Pickup
5A 5.00 .. 175.00 A; ∞∞A
1809 50c-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 50c-3 Time Delay
1901 50Nc-2 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; 7.00 A 50Nc-2 Pickup
5A 0.25 .. 175.00 A; 35.00 A
1902 50Nc-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 50Nc-2 Time Delay
1903 50Nc-1 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; 1.50 A 50Nc-1 Pickup
5A 0.25 .. 175.00 A; 7.50 A
1904 50Nc-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.30 sec 50Nc-1 Time Delay
1905 51Nc PICKUP ColdLoadPickup 1A 0.05 .. 4.00 A 1.00 A 51Nc Pickup
5A 0.25 .. 20.00 A 5.00 A
1906 51Nc T-DIAL ColdLoadPickup 0.05 .. 3.20 sec; 0.50 sec 51Nc Time Dial
1907 51Nc T-DIAL ColdLoadPickup 0.50 .. 15.00 ; 5.00 51Nc Time Dial
1908 50Nc-3 PICKUP ColdLoadPickup 0.05 .. 35.00 A; ∞∞A 50Nc-3 Pickup
1909 50Nc-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 50Nc-3 Time Delay
2008 67c-3 PICKUP ColdLoadPickup 1A 1.00 .. 35.00 A; ∞∞A 67c-3 Pickup
5A 5.00 .. 175.00 A; ∞∞A
2009 67c-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 67c-3 Time Delay
2101 67Nc-2 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; 7.00 A 67Nc-2 Pickup
5A 0.25 .. 175.00 A; 35.00 A
2102 67Nc-2 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 67Nc-2 Time Delay
2103 67Nc-1 PICKUP ColdLoadPickup 1A 0.05 .. 35.00 A; 1.50 A 67Nc-1 Pickup
5A 0.25 .. 175.00 A; 7.50 A
2104 67Nc-1 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.30 sec 67Nc-1 Time Delay
2105 67Nc-TOC PICKUP ColdLoadPickup 1A 0.05 .. 4.00 A 1.00 A 67Nc-TOC Pickup
5A 0.25 .. 20.00 A 5.00 A
2106 67Nc-TOC T-DIAL ColdLoadPickup 0.05 .. 3.20 sec; 0.50 sec 67Nc-TOC Time Dial
2107 67Nc-TOC T-DIAL ColdLoadPickup 0.50 .. 15.00 ;
5.00 67Nc-TOC Time Dial
2108 67Nc-3 PICKUP ColdLoadPickup 0.25 .. 35.00 A; ∞∞A 67Nc-3 Pickup
2109 67Nc-3 DELAY ColdLoadPickup 0.00 .. 60.00 sec; 0.00 sec 67Nc-3 Time Delay
2201 INRUSH REST. 50/51 Overcur. OFF
ON
OFF Inrush Restraint
2202 2nd HARMONIC 50/51 Overcur. 10 .. 45 % 15 % 2nd. harmonic in % of fundamen-
tal
2203 CROSS BLOCK 50/51 Overcur. NO
YES
NO Cross Block
2204 CROSS BLK TIMER 50/51 Overcur. 0.00 .. 180.00 sec 0.00 sec Cross Block Time
2205 I Max 50/51 Overcur. 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inrush Re-
straint
5A 1.50 .. 125.00 A 37.50 A
3101 Sens. Gnd Fault Sens. Gnd Fault OFF
ON
ON with GF log
Alarm Only
OFF (Sensitive) Ground Fault
3102 CT Err. I1 Sens. Gnd Fault 1A 0.001 .. 1.600 A 0.050 A Current I1 for CT Angle Error
5A 0.005 .. 8.000 A 0.250 A
Addr. Parameter Function C Setting Options Default Setting Comments