Appendix
A.9 Information List
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
481
2657 67N/67N-TOC is BLOCKED
(67N BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 14 1 Yes
2658 67N/67N-TOC is ACTIVE (67N
ACTIVE)
67 Direct. O/C OUT On
Off
**LEDBO63151Yes
2659 67N-1 is BLOCKED (67N-1
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 93 1 Yes
2668 67N-2 is BLOCKED (67N-2
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 94 1 Yes
2677 67N-TOC is BLOCKED (67N-
TOC BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 96 1 Yes
2678 67-3 TRIP (67-3 TRIP) 67 Direct. O/C OUT * on * LED BO
2679 67N-2 TRIP (67N-2 TRIP) 67 Direct. O/C OUT * on m LED BO 63 64 2 Yes
2681 67N-1 picked up (67N-1 picked
up)
67 Direct. O/C OUT * On
Off
* LED BO 63 41 2 Yes
2682 67N-1 Time Out (67N-1 Time
Out)
67 Direct. O/C OUT * * * LED BO 63 42 2 Yes
2683 67N-1 TRIP (67N-1 TRIP) 67 Direct. O/C OUT * on m LED BO 63 43 2 Yes
2684 67N-TOC picked up (67N-
TOCPickedup)
67 Direct. O/C OUT * On
Off
* LED BO 63 44 2 Yes
2685 67N-TOC Time Out (67N-TOC
TimeOut)
67 Direct. O/C OUT * * * LED BO 63 45 2 Yes
2686 67N-TOC TRIP (67N-TOC TRIP) 67 Direct. O/C OUT * on m LED BO 63 46 2 Yes
2687 67N-TOC disk emulation is
ACTIVE (67N-TOC Disk PU)
67 Direct. O/C OUT * * * LED BO
2691 67/67N picked up (67/67N
pickedup)
67 Direct. O/C OUT * On
Off
m LED BO 63 50 2 Yes
2695 67N/67N-TOC picked up (67N
picked up)
67 Direct. O/C OUT * On
Off
* LED BO 63 54 2 Yes
2696 67/67N TRIP (67/67N TRIP) 67 Direct. O/C OUT * on m LED BO 63 55 2 Yes
2697 67-3 picked up (67-3 picked up) 67 Direct. O/C OUT * On
Off
* LED BO
2698 67N-3 picked up (67N-3 picked
up)
67 Direct. O/C OUT * On
Off
* LED BO
2699 67-3 Time Out (67-3 Time Out) 67 Direct. O/C OUT * * * LED BO
2700 67N-3 Time Out (67N-3 Time
Out)
67 Direct. O/C OUT * * * LED BO
4601 >52-a contact (OPEN, if bkr is
open) (>52-a)
P.System Data 2 SP On
Off
**LEDBIBO
4602 >52-b contact (OPEN, if bkr is
closed) (>52-b)
P.System Data 2 SP On
Off
**LEDBIBO
4822 >BLOCK 66 Motor Startup
Counter (>BLOCK 66)
48/66/51M Motor SP * * * LED BI BO
4823 >66 Mot.St. Cnt: Emergency start
(>66 emer.start)
48/66/51M Motor SP On
Off
* * LED BI BO 168 51 1 Yes
4824 66 Motor Startup Counter OFF
(66 OFF)
48/66/51M Motor OUT On
Off
* * LED BO 168 52 1 Yes
4825 66 Motor Startup Counter
BLOCKED (66 BLOCKED)
48/66/51M Motor OUT On
Off
On
Off
* LED BO 168 53 1 Yes
4826 66 Motor Startup Counter
ACTIVE (66 ACTIVE)
48/66/51M Motor OUT On
Off
* * LED BO 168 54 1 Yes
4827 66 Motor Startup Counter TRIP
(66 TRIP)
48/66/51M Motor OUT On
Off
* * LED BO 168 55 1 Yes
4828 >66 Mot.St. Cnt:Reset
therm.memory rotor (>66 RM
th.repl.)
48/66/51M Motor SP On
Off
**LEDBIBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation