5237 81-2 TRIP (81-2 TRIP) 81 O/U Freq. OUT * on m LED BO 70 235 2 Yes
5238 81-3 TRIP (81-3 TRIP) 81 O/U Freq. OUT * on m LED BO 70 236 2 Yes
5239 81-4 TRIP (81-4 TRIP) 81 O/U Freq. OUT * on m LED BO 70 237 2 Yes
6503 >BLOCK 27 undervoltage pro-
tection (>BLOCK 27)
27/59 O/U Volt. SP * * * LED BI BO 74 3 1 Yes
6505 >27-Switch current supervision
ON (>27 I SUPRVSN)
27/59 O/U Volt. SP On
Off
* * LED BI BO 74 5 1 Yes
6506 >BLOCK 27-1 Undervoltage pro-
tection (>BLOCK 27-1)
27/59 O/U Volt. SP On
Off
* * LED BI BO 74 6 1 Yes
6508 >BLOCK 27-2 Undervoltage pro-
tection (>BLOCK 27-2)
27/59 O/U Volt. SP On
Off
* * LED BI BO 74 8 1 Yes
6509 >Failure: Feeder VT
(>FAIL:FEEDER VT)
Measurem.Superv SP On
Off
* * LED BI BO 74 9 1 Yes
6510 >Failure: Busbar VT (>FAIL: BUS
VT)
Measurem.Superv SP On
Off
**LEDBIBO74101Yes
6513 >BLOCK 59 overvoltage protec-
tion (>BLOCK 59)
27/59 O/U Volt. SP * * * LED BI BO 74 13 1 Yes
6530 27 Undervoltage protection
switched OFF (27 OFF)
27/59 O/U Volt. OUT On
Off
**LEDBO74301Yes
6531 27 Undervoltage protection is
BLOCKED (27 BLOCKED)
27/59 O/U Volt. OUT On
Off
On
Off
* LED BO 74 31 1 Yes
6532 27 Undervoltage protection is
ACTIVE (27 ACTIVE)
27/59 O/U Volt. OUT On
Off
**LEDBO74321Yes
6533 27-1 Undervoltage picked up
(27-1 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 33 2 Yes
6534 27-1 Undervoltage PICKUP
w/curr. superv (27-1 PU CS)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 34 2 Yes
6537 27-2 Undervoltage picked up
(27-2 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 37 2 Yes
6538 27-2 Undervoltage PICKUP
w/curr. superv (27-2 PU CS)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 38 2 Yes
6539 27-1 Undervoltage TRIP (27-1
TRIP)
27/59 O/U Volt. OUT * on m LED BO 74 39 2 Yes
6540 27-2 Undervoltage TRIP (27-2
TRIP)
27/59 O/U Volt. OUT * on * LED BO 74 40 2 Yes
6565 59-Overvoltage protection
switched OFF (59 OFF)
27/59 O/U Volt. OUT On
Off
**LEDBO74651Yes
6566 59-Overvoltage protection is
BLOCKED (59 BLOCKED)
27/59 O/U Volt. OUT On
Off
On
Off
* LED BO 74 66 1 Yes
6567 59-Overvoltage protection is
ACTIVE (59 ACTIVE)
27/59 O/U Volt. OUT On
Off
**LEDBO74671Yes
6568 59-1 Overvoltage V> picked up
(59-1 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO 74 68 2 Yes
6570 59-1 Overvoltage V> TRIP (59-1
TRIP)
27/59 O/U Volt. OUT * on m LED BO 74 70 2 Yes
6571 59-2 Overvoltage V>> picked up
(59-2 picked up)
27/59 O/U Volt. OUT * On
Off
* LED BO
6573 59-2 Overvoltage V>> TRIP (59-2
TRIP)
27/59 O/U Volt. OUT * on * LED BO
6801 >BLOCK 48 Motor Startup Time
Supervision (>BLOCK 48)
48/66/51M Motor SP * * * LED BI BO
6805 >48/14 Mot.St.Time Sup. Rotor
locked (>48 Rot. locked)
48/66/51M Motor SP * * * LED BI BO
6811 48 Motor Startup Time Supervi-
sion OFF (48 OFF)
48/66/51M Motor OUT On
Off
* * LED BO 169 51 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Related product manuals