Diagnostics
5.2 Error messages of the CP 243-1
CP 243-1
Operating Instructions, 03/2012, C79000-G8976-C244-02
111
Error byte Description Reaction/remedy Transfer mechanism
hex dec Byte offset in the
SM area
Return value
(ETHx_)
The connection could not be
established or was aborted
or an attempt was made to
execute a request and the
parameter assignment of
the HTTP server was not
correct.
Check connection path
to the communications
partner
Check HTTP server
configuration for
completeness
37
16#06 6 The response packet
contains logical errors
A new read/write
request can be
triggered.
Check the
configuration.
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#07 7 The read request failed A new read/write
request can be
triggered.
The parameters of the
read request should be
checked.
25 - 32 _XFR
16#08 8 The write request failed A new read/write
request can be
triggered.
The parameters of the
write request should be
checked.
25 - 32 _XFR
16#09 9 Channel not configured A new read/write
request with other
parameters can be
triggered.
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#0A 10 The channel is configured
as SERVER but an attempt
was made to trigger a
read/write request
A new read/write
request with other
parameters can be
triggered.
25 - 32 _XFR
16#0B 11 Previous read/write request
not yet completed.
A new read/write
request can be
triggered.
Evaluate "DONE"
return parameter of the
previous read/write
request
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#0C 12 Invalid request identifier A new read/write
request can be
triggered
25 - 32
34
35
_XFR
_EMAIL
_FTPC
16#0D 13 All data transfers are
aborted because a new
configuration was triggered
by the user program.
Restart of the system 25 - 32
33
34
_XFR
_CFG
_EMAIL