Diagnostics
5.2 Error messages of the CP 243-1
CP 243-1
Operating Instructions, 03/2012, C79000-G8976-C244-02
113
Error byte Description Reaction/remedy Transfer mechanism
hex dec Byte offset in the
SM area
Return value
(ETHx_)
16#1A 26 A memory area was
exceeded while files were
being transferred or the
specified length does not
match the actual length of
the file.
Check whether this file
has sufficient memory
space
Check configuration,
particularly the .fdb file
35 _FTPC
16#1B 27 Error during data transfer
using FTP
Check whether the FTP
server is configured
correctly
Check whether network
problems exist
Check configuration,
particularly the .fdb file
35 _FTPC
16#80 128 External 24 V power supply
is not present
Apply power or wait till
ready
25 - 37
_XFR
_CFG
_EMAIL
_FTPC
16#81 129 This channel is not ready or
is not operating correctly
Wait until ready
Evaluate the return
parameters of the
ETHx_CTRL
subroutine
_XFR
_CFG
_EMAIL
_FTPC
16#82 130 This channel is busy or the
START input parameter is
not set.
Wait until ready
Set the START input
parameter
_XFR
_CFG
_EMAIL
_FTPC
16#83 131 A request was started with
an illegal channel number
A new read/write
request can be
triggered
Check the user
program
_XFR
16#84 132 A request was started with
an illegal data block
number.
A new read/write
request can be
triggered
Check the user
program
_XFR
_EMAIL
_FTPC
Error messages in byte format