Diagnostics
5.2 Error messages of the CP 243-1
CP 243-1
Operating Instructions, 03/2012, C79000-G8976-C244-02
115
Error word Description Reaction/remedy Transfer mechanism
Hex dec Byte offset in the
SM area
Return value
(ETHx_)
16#003C 60 The configuration has an
invalid gateway address
Check the configuration 20, 21 _CTRL
16#003D 61 The configuration has an
invalid value in the keepalive
parameter
Check the configuration 20, 21 _CTRL
16#003E 62 No valid configuration
received from memory of the
S7-200 CPU or from
BOOTP/DHCP
Cyclic attempt to obtain
a valid configuration
either from the memory
of the S7-200 CPU or
via a BOOTP/DHCP
server
20, 21 _CTRL
16#0042 66 The NDB contains syntax
errors in the read/write
requests or length
information.
Check the configuration 20, 21 _CTRL
16#0093 147 The BOOTP/DHCP request
failed
Automatic restart 20, 21 _CTRL
16#0094 148 The reply of the
BOOTP/DHCP server
contains invalid data
Automatic restart 20, 21 _CTRL
16#0095 149 The TCP/IP stack did not
accept the specified
monitoring time (keepalive).
Automatic restart 20, 21 _CTRL
16#0096 150 The TCP/IP stack did not
accept the IP address
specified for a client.
Automatic restart 20, 21 _CTRL
16#0097 151 The TCP/IP stack did not
accept the specified subnet
mask.
Automatic restart
20, 21 _CTRL
16#0098 152 The TCP/IP stack did not
accept the specified gateway
address.
Automatic restart
20, 21 _CTRL
16#00B0 176 The IDB contains invalid
values.
Create configuration
with STEP 7 Micro/WIN
32
20, 21 _CTRL
16#00B1 177 The CRC check of the IDB
failed.
Create configuration
with STEP 7 Micro/WIN
32
Check the user program
to find out whether
configuration data was
accidentally overwritten
20, 21 _CTRL
16#00B2 178 No administrator name is
specified in the IDB.
Create configuration
with STEP 7 Micro/WIN
32
20, 21 _CTRL
16#00B3 179 The administrator password
check failed or no password
was specified
Create configuration
with STEP 7 Micro/WIN
32
20, 21 _CTRL