Installing
3.3 Installing Control Unit
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB
31
Default setting 17: Two-wire control
with method 2
All Control Units
Selected with
STARTER: 2-wire
(forward/backward 1)
BOP-2: 2-wIrE 1
Default setting 18: Two-wire control
with method 3
All Control Units
Selected with
STARTER: 2-wire
(forward/backward 2)
BOP-2: 2-wIrE 2
Default setting 19: Three-wire control
with method 1
All Control Units
Selected with
STARTER: 3-wire
(enable/forward/backward)
BOP-2: 3-wIrE 1
Fieldbus interface is not active.
The CU 240B-2 does not have terminals 16 and 17
Fieldbus interface is not active.
The CU 240B-2 does not have
terminals 16 and 17
Default setting 20: Three-wire control
with method 2
All Control Units
Selected with
STARTER: 3-wire
(enable/on/reverse)
BOP-2: 3-wIrE 2
Default setting 21: Fieldbus USS
All Control Units
Selected with
STARTER: USS fieldbus
BOP-2: FB USS
Default setting 22: Fieldbus CANopen
Control Units CU230P-2
Selected with
STARTER: CAN fieldbus
BOP-2: FB CAN
Fieldbus interface is not active.
The CU 240B-2 does not have
terminals 16 and 17
USS setting: 38400 baud, 2 PZD, PKW
variable
The CU 240B-2 does not have
terminals 16 and 17
CANopen setting: 20 kBaud
The default settings for BT inverters are also described in the operating instructions. See
also: Manuals for your inverter (Page 47).