Measured value data records
E.4 Measured value data record for maximum values (DS 144)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
237
E.4
Measured value data record for maximum values (DS 144)
E.4.1
Measured value data record for maximum values (DS 144) version 1
Measured variables of the module
The largest values ever measured or calculated from the time AI Energy Meter HF was
started are stored in this data record.
The measured value identification (measured value ID) is an index which references the
overview table of the measured variables in appendix B (Measured variables (Page 163)).
Byte
Measured variable
Data
type
Unit
Default
Meas-
ured
value
ID
0
Version
UINT8
-
0
-
1 Reserved UINT8 - 0 -
2...5
Max. voltage L1-N
REAL
V
0
40
6...9 Max. voltage L2-N REAL V 0 41
10...13
Max. voltage L3-N
REAL
V
0
42
14...17
Max. voltage L1-L2
REAL
V
0
43
18...21
Max. voltage L2-L3
REAL
V
0
44
22...25
Max. voltage L3-L1
REAL
V
0
45
26...29
Max. current L1
1
REAL
A
0
46
30...33
Max. current L2
1
REAL
A
0
47
34...37
Max. current L3
1
REAL
A
0
48
38...41
Max. apparent power L1
REAL
VA
0
49
42...45
Max. apparent power L2
REAL
VA
0
50
46...49
Max. apparent power L3
REAL
VA
0
51
50...53
Max. active power L1
REAL
W
-3.0 x 10
9
52
54...57
Max. active power L2
REAL
W
-3.0 x 10
9
53
58...61
Max. active power L3
REAL
W
-3.0 x 10
9
54
62...65
Max. reactive power Qtot L1
REAL
var
-3.0 x 10
9
62160
66...69
Max. reactive power Qtot L2
REAL
var
-3.0 x 10
9
62260
70...73
Max. reactive power Qtot L3
REAL
var
-3.0 x 10
9
62360
74...77
Max. power factor λ L1
REAL
-
0
58
78...81
Max. power factor λ L2
REAL
-
0
59
82...85 Max. power factor λ L3 REAL - 0 60
86...89
Max. frequency
REAL
Hz
45
61
90...93
Max. apparent power L1L2L3
REAL
VA
0
67
94...97
Max. active power L1L2L3
REAL
W
-3.0 x 10
9
65
98...101
Max. reactive power Qtot L1L2L3
REAL
var
-3.0 x 10
9
61138

Table of Contents

Other manuals for Siemens DI 8x24VAC/48VUC BA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens DI 8x24VAC/48VUC BA and is the answer not in the manual?

Siemens DI 8x24VAC/48VUC BA Specifications

General IconGeneral
BrandSiemens
ModelDI 8x24VAC/48VUC BA
CategoryI/O Systems
LanguageEnglish

Related product manuals