EasyManua.ls Logo

Siemens DPU Series - Floor Interlock and Operating Lever Adjustment

Siemens DPU Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
11
The circuit breaker must be open and discharged prior to removing any covers.
Adjustment tool 18-671-185-059, Steel Bar, 0.38 x 1.25 x 19.5 inches
Tools required:
1/2 inch wrench or socket (5DPR only)
• Midsize flat tip screwdriver
7/16 inch wrench or socket
• Adjustment tool 18-671-185-059
9/16 inch open end wrench
Step 1
Move circuit breaker on to a smooth flat surface
m
m
Loosen hex-jam nut using a 9/16 inch wrench on
indicated clevis by turning it counterclockwise.
Turning
the 3/8 inch rod counterclockwise
moves
the
roller down (decreasing clearance between
floor
and roller).
Turning the 3/8 inch rod clockwise moves the roller
up (increasing clearance between floor and roller).
Floor Interlock and Operating Lever Adjusting Instructions