CHAPTER 2 | DEVICE PROGRAMMING UNIT USER’S MANUAL
PROGRAMMING 11
1b
6
5
1a
DPU DB-3S BASE
ADAPTOR
P/N 515-033925
BOTTOM
OF DPU
*NOTE:
The prong on the same side
of the programming plug as the
locating tab goes into the black
banana jack.
*LOCATING
TAB
PROGRAMMING
PLUG
BLACK
BANANA
JACK
To Program/Test A Compatible Series ILI/ILP
Detector, connect the DPU to the DB-3S Base
Adaptor:
To Remove Detector Head:
• Insert programming plug of P/N 515-033925 into
the red and black banana jacks in the cable
compartment in the bottom of the DPU.
• Align notch in detector cover to raised surface
on outer ring of base.
• Push detector head into base and rotate
clockwise to make electrical connections. The
detector automatically stops and locks into
place.
• Push detector head into the base while rotating
the detector head counterclockwise. Continue
to rotate counterclockwise until stop is
reached.
CABLE P/N 555-133891
WITH ALLIGATOR CLIPS
BOTTOM OF DPU
O
R
GBL
K
BLK
G
R
N
O
R
GRE
D
RED
A
L
L
C
O
N
N
E
C
T
IO
N
S
A
R
E
P
O
W
E
R
L
IM
IT
E
D
-
E
A
R
T
H
G
N
D
+
HTRI-M
To Program/Test HTRI-M/TRI-B6M Devices:
• Insert the programming plug in one end of cable
P/N 555-133891 into the red and black banana
jacks in the cable compartment in the bottom of
the DPU.
• Using the two alligator clip adaptors provided on
the programming plug, connect the other end of
cable P/N 555-133891 to the red and black wires
of the HTRI/TRI device.
*
LOCATING TAB
PROGRAMMING
PLUG
BLACK
BANANA
JACK
*NOTE:
When programming or testing MXL
and FS-100 devices, the prong on
the same side of the programming
plug as the locating tab goes into
the black banana jack.