Parameters/address space
3.3 Address space
Server module (6ES7193-6PA00-0AA0)
Manual, 03/2015, A5E03575337-AB
11
The length of the input data depends on the CPU/interface module:
● Interface module with 12 I/O modules maximum configuration: 2/4 bytes
● Interface module with 32 I/O modules maximum configuration: 4/8 bytes
● CPU/interface module with 64 I/O modules maximum configuration: 8/16 bytes
In the configuration software, you can select 3 configurations for the server module for
operation on the CPU/interface module:
● Configuration with disabled "Status of the supply voltage L+" and disabled "Status of the
feedback voltage":
– The server module only has one diagnostics address.
● Configuration with enabled "Status of the supply voltage L+" and disabled "Status of the
feedback voltage":
– The server module has 2/4/8 bytes of input data for the display of the status of the
supply voltage L+ of the inserted I/O modules.
– Display in the input data of the server module:
Supply voltage L+ present/missing or I/O module available/not available
● Configuration with enabled "Status of the supply voltage L+" and enabled "Status of the
feedback voltage":
– The server module has 4/8/16 bytes of input data for the display of the status of the
supply voltage L+ and the status of the feedback voltage of the inserted I/O modules.
– Display in the input data of the server module:
Supply voltage L+ present/missing or I/O module available/not available
Feedback voltage present/missing
Table 3- 2 Data length depending on configuration and maximum configuration