Parameters/address space
3.3 Address space
Server module (6ES7193-6PA00-0AA0)
12 Manual, 03/2015, A5E03575337-AB
3.3.1
Input data for interface modules with maximum 12 I/O modules
Configuration with enabled status detection of the supply voltage L+ (2 bytes of input data)
You can read out the following status for each I/O module of the ET 200SP in the input data
(byte 0 to 1):
Supply voltage L+ present/missing or I/O module available/not available (2 bytes)
Figure 3-1 Configuration with enabled status detection of the supply voltage L+ (2 bytes)
Configuration with enabled status detection of the supply voltage L+ and enabled status detection of
the feedback voltage (4 bytes of input data)
You can read out the following status for each I/O module of the ET 200SP in the input data
(byte 0 to 3).
Supply voltage L+ present/missing or I/O module available/not available (2 bytes)
Feedback voltage present/missing (2 bytes)
Figure 3-2 Configuration with enabled status detection of the supply voltage L+ and enabled status
detection of the feedback voltage (4 bytes of input data)
Note
An inserted or missing server module always signals bit=0 for the slot.
If the server module is missing, the input data is invalid.
For I/O modules without feedback voltage monitoring, the bit for the feedback voltage is
the same as the bit for the missing supply voltage L+.