Programming Manual of FC2005/FC901
A6V10333724_b_en_-- 3|63
· DACT: The Digital Alarm Communication Transmitter board which will send control panel status data to a
remote receiving station.
· DACT Connection: DACT has two physical connections to PSTN, two telephone lines. One is the
main connection and the other is used as backup connection.
· DACT Network: The DACT has two accounts and each account can be configured separately.
· UFP: Serial Interface Circuit.
· The serial interface circuit can address up to 8 devices, which includes annunciators and printers.
Up to 2 printers can be addressed. Devices on the circuit may be connected up to 4000 feet from
the control panel.
· CityTie/LeaseLine
· CTLL is one optional module which can be mounted onto the mainboard of FC2005/FC901. if the
module is installed and enabled in the hardware tree, the work mode of this output can be
configured to City Tie or Lease Line.
· Program Key: the programmable key is used to execute the user defined and configured functions.
Supported functions are: DACT bypass, Addressable device bypass, NAC bypass, Fire drill, Manual
evacuation, Co test and Lamp test.
Detection tree:
The Detection tree contains the zones used for report different types of events. The supported zone types
include:
· Manual alarm zone
· Automatic alarm zone
· Waterflow zone
· Supervisory zone
· Trouble zone
· Status zone
· AC Fail zone
· Gas zone
There are two default zones:
· Manual Alarm Zone1:
· Automatic Alarm Zone1:
The system will create a new zone for each new added channel automatically. User can add or delete the
zones except the two default zones. If users delete a zone, the channels in the zone will be reassigned to the
default zone according to the types.
Control tree:
The control tree contains all control logics. The causes of the control logic can be the control panel, zones
and channels. The effects should be outputs, relays and NACs.
There are two default control logic:
· Control 1: There is no device in the cause and the effect is programmable relay.
· Adv. Control 1: The cause of the logic is the control panel. This control logic is used to realize the
conditional activation of the City Tie, Lease Line, alarm/supervisory/trouble relays and the NACs.
The criterion is configured at devices in effect.
Dialer Group: