EasyManua.ls Logo

Siemens FDA221

Siemens FDA221
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Planning
Operating modes
40
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
4.2.1 Parameter Sets
The following information applies to the 'Automatic: switches between blue and
blue-red based on ratio' mode.
FDA241
Set
No.
Sensitivity [%/m]
Comment
Inspect
Prealarm
Fire 1
Fire 2
0 0.07 0.10 0.15 20 default
1 0.03 0.04 0.05 2 -
2 0.03 0.045 0.06 2.5 -
3 0.04 0.055 0.07 3 -
4 0.05 0.075 0.10 4 -
5 0.07 0.10 0.15 5 -
6 0.08 0.14 0.20 6 -
7 0.18 0.28 0.40 8 -
8 0.30 0.50 0.70 10 -
9 0.40 0.70 1.00 15 -
10 0.80 1.40 2.00 20 -
FDA221
Set no.
Sensitivity [%/m]
Comment
Prealarm
Fire 1
Fire 2
0 0.50 0.70 20 default
6 0.14 0.20 6 -
7 0.28 0.40 8 -
8 0.50 0.70 10 -
9 0.70 1.00 15 -
10 1.40 2.00 20 -