You know the ambient conditions such as temperature and air humidity.
You know the movements of air such as natural airflows and ventilation from air
conditioning systems in the area being monitored.
You know what the building material is, e.g., concrete, wood or brick, so you
can fasten the pipe system correctly.
You know the ambient conditions such as whether the environment is dirty or
dusty, and other external influences.
The preferred application has been defined for the aspirating smoke detector,
e.g., room protection or equipment protection.
In case of pressure differences:
If the aspirating smoke detector is mounted outside the area being monitored, it
may be necessary to return the aspirated air to the area being monitored via a
return pipe.
Connecting external devices
Various external devices can be connected to the aspirating smoke detector.
10
9
8
6
5
4
3
2
1
Fig. 1: Connecting external devices FDA221, FDA241
System description
3
A6V11783979_en--_a 13 | 48

Other manuals for Siemens FDA241 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA241 Series and is the answer not in the manual?

Siemens FDA241 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA241 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals