Specifications
Technical data
8
29 |
Building Technologies
A6V10201150_d_en_
--
Fire Safety
2018
-
-
19
8 Specifications
8.1 Technical data
Detector line Operating voltage DC 16…26 V
Quiescent current 0.01 mA
Alarm current (permanent, maximum) 60 mA
Alarm current (pulsating) 100 mA
Maximum current connection factor 1
Quiescent current connection factor 1
Protocol Collective (SynoLINE600)
Compatibility
Refer to document 'List of compatibility';
doc. no. 008331
Connections Detector line:
Design Screw terminals
Cable cross section 0.28…1.5 mm
2
Ambient conditions Operating temperature -25…+70 °C
Storage temperature -30…+75 °C
Air humidity 95 % rel.
Protection category (IEC60529) IP44
Electromagnetic compatibility at:
10 MHz…1 GHz 50 V/m
1 GHz…2 GHz 10 V/m
Mechanical data Dimensions (L x W x H):
FDM1101-Rx 87 x 87 x 20 mm
FDM1101-Rx with back box
FDMH295-R / FDMH295-S
87 x 87 x 53 mm
Weight:
FDM1101-Rx 0.097 kg
Back box FDMH295-R /
FDMH295-S
0.057 kg
Colors:
FDM1101-Rx Red (RAL 3000)
Back box FDMH295-R /
FDMH295-S
Red (RAL 3000)
Material ABS PC ASA
Standards European standards EN 54-11
EN 50130-4