Repairs
44
Building Technologies FL-III Maintenance and Repair
CPS Fire Safety 08.2012
Fig. 33 Locking for the fixation of the riser card
After completion of the work, a functional test and commissioning of the controller
is required.
WARNING!
After installation or replacement of a riser card and additional
interface cards, ALL inputs and outputs must be tested.
Replacement of the interface panel
Disassembly
1 Remove the three screws of the interface panel on the housing floor.
2 Remove the three screws of the interface panel on the digital board.
3 Remove the cover of the CF memory card slot (fig. 16). Remove the two
screws of the interface panel on the CF board located under that cover.
4 Remove the six threaded bolts of the standard interface panel on the Sub-D
connectors. If additional interface cards are already present, then their
threaded bolts must also be removed.
5 Remove the interface panel.
Fig. 34 Removal of the interface panel
(Example with the standard interface panel)