Transport, installation and assembly 
  3.10 Connection of the machine 
A5E01083943A AB       
Siemens AG Operating Instructions 2.02 1FW4  
53 
Connecting using cable lugs 
When using cable lugs to make the connection, the choice of cable lug size must match the 
required conductor cross-section and the bolt size. A sloped/angular arrangement is only 
permitted provided the required air insulation gaps are met. Remove the insulation from the 
conductor ends so that the remaining insulation is almost long enough to reach the cable lug.  
 
 
Note 
The current-carrying capacity of the connection is guaranteed using the CuZn contact nuts. 
These nuts must not be replaced by parts made from other materials. 
 
Connection without cable lugs 
The design of the terminals makes it possible to connect fine-wire conductors without the 
use of wire end ferrules. Wire end ferrules should only be used if they are attached to the 
conductor before connection, using an appropriate, current-carrying compression 
connection. 
 
NOTICE 
 
If terminal links are used, the current-carrying connection is guaranteed using CuZn contact 
nuts. These nuts must not be replaced by parts made from other materials. 
 
Aluminum conductors 
If aluminum conductors are connected, we recommend removing the oxide coating layer 
using a brush or file prior to inserting them in the clamps. The conductors should then be 
immediately greased using neutral Vaseline in order to prevent re-oxidation. 
 
NOTICE 
 
Aluminum flow is likely to occur after the conductors have been connected due to the 
contact pressure. This should be compensated for by re-tightening the clamping nuts after 
approximately 24 hours and then again after approximately 4 weeks. 
 
Use of single-stranded cables 
When high currents and several single-core conductors are used instead of stranded cables 
in the cable entry port area, high temperatures result due to eddy currents. After 
commissioning, ensure that the temperature limits of the connected power cables are not 
exceeded during operation. This temperature effect can be reduced by altering the 
conditions at the entry points or by using modified cable entry plates after consultation with 
the manufacturing plant.