109/301 
Siemens Building Technologies  Basic Documentation LMV5...  CC1P7550en 
HVAC Products  7 Display and operating unit AZL5...  13.08.2004 
 
 
- Continue with 
Enter 
⇓ 
P o  i  n t  |  L o a d    :  2 3  .  5 
  :  3 | F u e l  : 2 3 . 2 
 O 2      | A i r      : 4 1 . 6 
   4 . 5 | A u x     : 3 3 . 3 
 
It is to be noted that with these settings, which can be made in standby and normal op-
eration, the actuators will travel to the displayed or changed positions. 
Traveling to the load that is assigned to the curvepoint can be stopped by pressing 
Esc. 
During the time the actuators approach the positions, the display shows « 
> » in place of 
« 
: ». 
 
Note: If a new point is introduced, the point‘s data to be entered are the actual values. 
 
The parameter that shall be changed (e.g. the fuel position) can be selected by chang-
ing the pointer position. 
 
P o i n t | L o a d  : 2 3 . 5 
  :  3 | F u e l    : 2 3 . 2 
 O 2      | A i r      : 4 1 . 6 
   4 . 5 | A u x     : 3 3 . 3 
 
After the selected point of curve has been reached by the system: 
- Continue with 
Enter 
⇓ 
P o i n t | L o a d  : 2 3 . 5 
  :  3 | F u e l  : 2 3 . 2 
 O 2      | A i r      : 4 1 . 6 
   4 . 5 | A u x     : 3 3 . 3 
 
Now, the selected parameter can be changed online. This means that the system fol-
lows the changes at the rate of the selected ramp speed. Press 
Enter to save the 
changed values. 
Now, additional parameters for change can be selected. 
If 
Esc is pressed before Enter, changes made to the selected parameter (e.g. fuel posi-
tion) will be rejected and the value last saved will be restored. 
 
When leaving this level with 
Esc, the following query appears: 
 
P o i n t  
S t o r e  - > E N T E R 
C a n c e  l        - > E S C     
 
 
Enter
 saves the changes or the new point and adds them to the already existing points 
in the correct order (during the storage process, no buttons will be evaluated. 
To indicate this, a symbol appears on the display). 
The changes can be rejected by pressing
 Esc.